RTD PT100 TEMPERATURE TRANSMITTER  TxPT2
  • Compact size
  • 2 - wire Transmitter Connection
  • ZERO and SPAN adjustment (from front panel)
  • LED indication
  • 35 mm DIN rail mounting
  • Flame Retardant ABS enclosure
 Key Specifications
 
Type Two wire
Input RTD PT100 (DIN 43760)
Supply voltage 12 to 35V DC
Output signal 4 to 20 mA non-isolated
   
 
TxPT2 RTD PT100 Temperature Transmitter converts an analog signal from a PT100 resistance thermometer to a 4 - 20 mA output signal. It is designed for a two-wire connection in which the supply current value conveys the information about temperature. The voltage drop at the resistance thermometer is amplified by an operational amplifier and converted to an output current of 4 - 20 mA. These transmitters make it possible to adjust both gain and zero. Zero and span adjustments can be done through trimmers present on the front panel. The transmitter can recognize a broken wire or a short-circuited resistance thermometer.

 